Loading

 
         
 
       
         
 
 
 
1
2
3
4
5
 
ÏÁáÏíã-HF 2x10-1
ÒÓ Ó 31.3-00214534-069:2012
Power cables with copper conductors, with halogen-free polymer compound insulation, galvanized steel-tape armoured, with polymer compound outer sheath, flame-retardant, halogen-free
Cables are used for laying:
• in places, where small mechanical impacts on cable are possible, including tensile forces
• power supply cable lines of NPP electric equipment, wiring in office premises , which are computerized and intelligent, in kindergartens, schools, hospitals and for cable lines of spectating complexes and sport structures
Fire safety code in accordance with ÄÑÒÓ 4809:2007: ÏÁ123122000
Products of this mark meet the requirements:
• single wire cable flame retardance
• bunched cable flame retardance category A
• toxicity class Tk3 of the combustion products of nonmetallic elements (toxicity index over 120 g/m3)
• class ÄÒê1 on smoke-forming ability by smouldering of non-metallic elements (coefficient of smoke formation from 50 to 500 m2/kg)
• class ÄÏê2 on smoke-forming ability by combustion (minimum luminous flux more than 60 %)
• corrosive class Êê2 of combustion products of non-metallic elements (the number of halogen hydrides less than 150 mg/g, pH more than 4.3, specific conductivity less than 10 µS/mm)