ÀÏâÝîÂíãä(ê)-20 3x240 ÒÓ Ó 31.3-00214534-017-2003 |
Three-core power cables with aluminium conductors, flame-retardant, with XLPE, collective screen and PVC compound outer sheath, with low smoke and gas emission |
Technical cable requirements correspond to IEC 60502-2 |
|
|
|
Cables are used for laying: |
• in premises, tunnels, ducts, mines, dry soil and outdoor under shelter |
• in bunches |
• at sites, where low smoke and gas emission are required (NPP, subway, large industrial facilities, high-rise buildings, etc.) |
|
|
|
It is possible to manufacture cables with an integrated fiber-optic module. Order entry example: |
ÀÏâÝîÂíãä(ê)-20 3x240/70 (ÎÌ) ÒÓ Ó 31.3-00214534-017-2003 |
In conjunction with the DTS system, the integrated fiber-optic module can act as a distributed cable line temperature sensor. To learn more. |
|
|
|
It is possible to manufacture cable with sealed conductors. Order entry example: |
ÀÏâÝîÂíãä(ê)-20 3x240/70 (ã) ÒÓ Ó 31.3-00214534-017-2003 |
|
|
|
Fire safety code in accordance with ÄÑÒÓ 4809:2007: ÏÁ132121000 |
Products of this mark meet the requirements: |
• single wire cable flame retardance |
• bunched cable flame retardance category B |
• toxicity class Tk2 of the combustion products of nonmetallic elements (toxicity index from 40 up to 120 g/m3) |
• class ÄÒê1 on smoke-forming ability by smouldering of non-metallic elements (coefficient of smoke formation from 50 to 500 m2/kg) |
• class ÄÏê2 on smoke-forming ability by combustion (minimum luminous flux more than 60 %) |
• corrosive class Êê1 of combustion products of non-metallic elements (the number of halogen hydrides less than 150 mg/g, pH less than 4.3, specific conductivity more than 10 µS/mm) |