1
2
3
4
5
 
ÊÂÂÃíãä-FR 4x6
ÒÓ Ó 31.3-00214534-055:2006
Control flame-retardant flame-resistant cables with copper conductors, low fire-risk PVC compound insulation, PVC compound sheath, low smoke and gas emission
Cables are used for laying:
• in premises, dry ducts and tunnels, in corrosive environment
• with no risk of mechanical damage in operation
• in bunches, in crowded places
• power supply cable lines of NPP safety system equipment, circuits wiring of fire safety systems (fire alarm circuits, power supply of fire-fighting pumps, lightning of emergency exits and evacuation routes, smoke exhaust and blowing ventilation systems, evacuation elevators); for wiring in hospital surgical wings, emergency and equipment (current collectors) power supply circuits, operating in a fire emergency
Manufacturing of extruded fire-resistant barrier is possible
Fire safety code in accordance with ÄÑÒÓ 4809:2007: ÏÁ123121080
Products of this mark meet the requirements:
• single wire cable flame retardance
• bunched cable flame retardance category A
• toxicity class Tk3 of the combustion products of nonmetallic elements (toxicity index over 120 g/m3)
• class ÄÒê1 on smoke-forming ability by smouldering of non-metallic elements (coefficient of smoke formation from 50 to 500 m2/kg)
• class ÄÏê2 on smoke-forming ability by combustion (minimum luminous flux more than 60 %)
• corrosive class Êê1 of combustion products of non-metallic elements (the number of halogen hydrides less than 150 mg/g, pH less than 4.3, specific conductivity more than 10 µS/mm)
• flame-resistant class FE180 under fire conditions with a temperature not less than 750 °Ñ